Permanent Service | 5/22/2003 | 5/23/2003 | 5/23/2003 | A | PASS |
Jack Frank
|
|
|
8:00 am meeting with Rick p/s o/h rec. ok 5/23/2003 8:52:41 AM
|
DOC - Permit Finaled | 5/23/2003 | 5/23/2003 | 5/23/2003 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 5/23/2003 8:52:55 AM
|
Final | 5/21/2003 | 5/22/2003 | 5/22/2003 | P | CANC |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/21/2003 at 8:55:05 PM. Contact: ###-####. will meet owner 05/23/03 8:00 am 5/22/2003 1:41:56 PM
|
Permanent Service | 5/14/2003 | 5/15/2003 | 5/15/2003 | P | FAIL |
Jack Frank
|
|
|
###-#### back door unlocked or call for access cor. posted called 250.92(A)(3) bond both ends of nipple between meter and panel, 250.104(A)(1) jumper around dielectric union in basement, 110.26(F)(1) clearence sub panel in basement, use manufactures listed equip grd bus 5/15/2003 2:09:46 PM
|
Electrical Rough-In | 4/11/2003 | 4/14/2003 | 4/14/2003 | A | NH |
Jack Frank
|
|
|
###-#### please call multi state elec for access called left message 4/14/2003 8:20:12 AM called no response back 4/14/2003 12:21:05 PM
|
Issue & PRINT permit | | | 4/11/2003 | | DONE |
|
|
|
|
Application received | | | 4/11/2003 | | |
|
|
|
|