Second Notice ELE | 10/23/2003 | 10/23/2003 | 11/14/2003 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 10/13/2003 | 10/23/2003 | | DONE |
|
|
|
|
DOC - Permit Finaled | 10/13/2003 | 10/13/2003 | 10/13/2003 | P | PASS |
Pat Lass
|
|
|
Finaled by inspector at 10/13/2003 3:01:16 PM
|
Rough-In Permanent Service | 10/10/2003 | 10/13/2003 | 10/13/2003 | P | PASS |
Pat Lass
|
|
|
DONNY; Phone #: ###-#### Internet Inspection Request from: Darla Downs
P/S O/H R Ok 10/13/2003 3:01:14 PM
|
Permanent Service | 9/23/2003 | 9/24/2003 | 9/24/2003 | P | NR |
Pat Lass
|
|
|
donny; Phone #: ###-#### Internet Inspection Request from: Annette Moore
after 3:00 9/23/2003 3:40:13 PM
|
Final | 9/12/2003 | 9/15/2003 | 9/15/2003 | A | FAIL |
Pat Lass
|
|
|
DONNY; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
8' ABOVE ROOF, LOOSE CONNECTORS,
cu/al under one lug, id neut, directory required, strap emt, seal unused opening , and streighten out MC cable. 9/15/2003 10:30:10 AM
|
Permanent Service | 8/8/2003 | 8/11/2003 | 8/11/2003 | P | FAIL |
Pat Lass
|
|
|
donny; Phone #: ###-#### Internet Inspection Request from: Annette Moore
service location and clearances won't work.
request conf. 8/11/2003 12:34:33 PM
|
Application received | | | 8/1/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 8/1/2003 | | DONE |
|
|
|
|