Permanent Service | 8/15/2003 | 8/18/2003 | 8/18/2003 | A | FAIL |
Jack Frank
|
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie needs bond bushings both ends of nipple, and terminate GEC to neutral bus, remove old GEC 8/18/2003 8:23:52 AM
|
Final | 8/18/2003 | 8/18/2003 | 8/18/2003 | P | PASS |
Joe Ray
|
|
|
ROGER; Phone #: ###-#### Internet Inspection Request from: Darla Downs p/s oh r ok 8/18/2003 1:38:40 PM
|
DOC - Permit Finaled | 8/18/2003 | 8/18/2003 | 8/18/2003 | P | PASS |
Joe Ray
|
|
|
Finaled by inspector at 8/18/2003 1:39:25 PM
|
Permanent Service | 8/6/2003 | 8/12/2003 | 8/12/2003 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 250.92 bond nipple at p/s, 250.52(A)(1) grd water within 5 ft bond around di electrics bond hot and cold , 250.66 needs #4 copper for grd and bonds, 250.53 2 grd rods, 230.24 8ft over roof and support mast 8/12/2003 3:14:49 PM
|
Issue & PRINT permit | | | 8/6/2003 | | DONE |
|
|
|
|
Application received | | | 8/6/2003 | | |
|
|
|
|