Permit Information
Permit NumberELE03-02394
StatusFinaled
Name GOODMAN ELECTRIC
Site Address 4502 W CASSIA ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service8/15/20038/18/20038/18/2003AFAIL
DetailsJack Frank
roger; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie needs bond bushings both ends of nipple, and terminate GEC to neutral bus, remove old GEC 8/18/2003 8:23:52 AM
Final8/18/20038/18/20038/18/2003PPASS
DetailsJoe Ray
ROGER; Phone #: ###-#### Internet Inspection Request from: Darla Downs p/s oh r ok 8/18/2003 1:38:40 PM
DOC - Permit Finaled8/18/20038/18/20038/18/2003PPASS
DetailsJoe Ray
Finaled by inspector at 8/18/2003 1:39:25 PM
Permanent Service8/6/20038/12/20038/12/2003PFAIL
DetailsJack Frank
###-#### cor. posted called 250.92 bond nipple at p/s, 250.52(A)(1) grd water within 5 ft bond around di electrics bond hot and cold , 250.66 needs #4 copper for grd and bonds, 250.53 2 grd rods, 230.24 8ft over roof and support mast 8/12/2003 3:14:49 PM
Issue & PRINT permit  8/6/2003 DONE
Application received  8/6/2003