Final | 8/12/2003 | 8/12/2003 | 8/12/2003 | P | PASS |
Jack Frank
|
|
|
Corrections performed.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchellok 8/12/2003 1:46:52 PM
|
Permanent Service | 8/12/2003 | 8/12/2003 | 8/12/2003 | P | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|
DOC - Permit Finaled | 8/12/2003 | 8/12/2003 | 8/12/2003 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 8/12/2003 1:47:46 PM
|
Final | 8/7/2003 | 8/8/2003 | 8/8/2003 | A | FAIL |
Jack Frank
|
|
|
1)We installed a 100amp power pedestal beside the Idaho Power pad-mount transformer in the Common Area of the condo complex, along with 2 ground rods.
2)We mounted a back-board beside this pedestal and ran a 20amp 120volt ckt.to it for a weatherproof GFCI receptacle.
3)We ran a 20amp 220volt ckt.to the back-board for a pump-start relay and a manual over-ride switch for the sprinkler pump.
3)We ran the pump ckt. in IMC out to the pump location and installed a 20amp 220volt single weatherproof receptacle for the pump.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. posted called 250.8, 314.3, 110.3(B) no sq d breakers allowed 8/8/2003 11:09:45 AM
|
Application received | | | 8/7/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 8/7/2003 | | DONE |
|
|
|
|
Telephone Call | | | | | |
|
|
|
|