Second Notice ELE | 1/22/2004 | 1/22/2004 | 1/28/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 1/7/2004 | 1/22/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 1/7/2004 | 1/7/2004 | 1/7/2004 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 1/7/2004 2:20:11 PM
|
Final | 1/7/2004 | 1/7/2004 | 1/7/2004 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/7/2004 at 7:16:03 AM. Contact: ###-####. ok card signed
1/7/2004 2:20:06 PM
|
Final | 1/5/2004 | 1/5/2004 | 1/5/2004 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/5/2004 at 7:11:52 AM. Contact: ###-####. not ready and cor. posted 210.8(B) gfci for all outlets in bathrm area, 620.52 warning signs for elevator disconnects, 400.8 shall not use cord as fixed wiring 1/5/2004 3:37:14 PM
|
Electrical Rough-In | 12/31/2003 | 12/31/2003 | 12/31/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/31/2003 at 6:54:59 AM. Contact: ###-####. ceilings ok print marked 12/31/2003 8:28:21 AM
|
Electrical Rough-In | 12/30/2003 | 12/30/2003 | 12/30/2003 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 12/30/2003 at 6:55:05 AM. Contact: ###-####.
anop
remove tiles 12/30/2003 1:43:06 PM
|
Electrical Rough-In | 12/18/2003 | 12/19/2003 | 12/19/2003 | P | NR |
Jack Frank
|
|
|
PLEASE PAGE LUKE BUSACK WITH ANY QUESTIONS- THE INSPECTION IS FOR VAULTED CEILING.
; Phone #: ###-#### Internet Inspection Request from: Jeff Radford contractor called in wrong permit , inspection neede at ST Als 12/19/2003 12:51:48 PM
|
Electrical Rough-In | 12/15/2003 | 12/15/2003 | 12/15/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/15/2003 at 6:56:30 AM. Contact: ###-####. conference ok 12/15/2003 11:02:51 AM
|
Electrical Rough-In | 12/15/2003 | 12/15/2003 | 12/15/2003 | P | PART |
Jack Frank
|
|
|
potting compound ok
|
Rough-In Permanent Service | 12/10/2003 | 12/10/2003 | 12/10/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/10/2003 at 7:01:34 AM. Contact: ###-####. p/s u/g new ok 12/10/2003 10:47:48 AM
|
Electrical Rough-In | 12/3/2003 | 12/3/2003 | 12/3/2003 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/3/2003 at 7:04:27 AM. Contact: ###-####. walls 2nd floor 12/3/2003 3:26:35 PM
|
Electrical Rough-In | 11/24/2003 | 11/24/2003 | 11/24/2003 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/24/2003 at 7:00:21 AM. Contact: ###-####. 1st floor N half prints marked 11/24/2003 1:02:49 PM
|
Electrical Rough-In | 11/20/2003 | 11/20/2003 | 11/20/2003 | P | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 11/20/2003 at 7:15:39 AM. Contact: ###-####. r/i walls and hard lid as marked on print ok 11/20/2003 3:18:28 PM
|
Electrical Rough-In | 10/22/2003 | 10/22/2003 | 10/22/2003 | P | PART |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 10/22/2003 at 7:06:00 AM. Contact: ###-####. 1st floor u/g ok 10/22/2003 2:56:01 PM
|
Electrical Rough-In | 10/21/2003 | 10/21/2003 | 10/21/2003 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/21/2003 at 6:58:28 AM. Contact: ###-####. u/g 1st floor middle section 10/21/2003 10:29:27 AM
|
Electrical Rough-In | 9/25/2003 | 9/26/2003 | 9/26/2003 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/25/2003 at 11:48:21 AM. Contact: ###-####. pool u/g ok 9/26/2003 9:45:54 AM
|
Electrical Rough-In | 9/25/2003 | 9/25/2003 | 9/25/2003 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/25/2003 at 7:17:32 AM. Contact: ###-####. u/g for pool needs 18" depth, and over 4 90 degree bends 9/25/2003 8:52:28 AM
|
Electrical Rough-In | 9/15/2003 | 9/15/2003 | 9/15/2003 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/15/2003 at 7:23:09 AM. Contact: ###-####. pool and spa bond 9/15/2003 12:04:29 PM
|
Electrical Rough-In | 8/21/2003 | 8/21/2003 | 8/21/2003 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/21/2003 at 8:22:52 AM. Contact: ###-####. electrode ok 8/21/2003 2:18:47 PM
|
Electrical Rough-In | 8/13/2003 | 8/13/2003 | 8/13/2003 | P | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 8/13/2003 at 8:11:56 AM. Contact: ###-####. under ground for parking lot lights ok for cover 8/13/2003 4:17:14 PM
|
Application received | | | 8/12/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 8/12/2003 | | DONE |
|
|
|
|