Second Notice ELE | 12/2/2003 | 12/2/2003 | 12/19/2003 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 11/17/2003 | 12/2/2003 | | DONE |
|
|
|
|
DOC - Permit Finaled | 11/17/2003 | 11/17/2003 | 11/17/2003 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 11/17/2003 2:57:27 PM
|
Final | 11/17/2003 | 11/17/2003 | 11/17/2003 | P | PASS |
Jack Frank
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 11/17/2003 2:57:21 PM
|
Final | 9/23/2003 | 9/23/2003 | 9/23/2003 | P | CANC |
Jack Frank
|
|
|
corey; Phone #: ###-#### Internet Inspection Request from: Annette Moore see added p/s 9/23/2003 12:21:22 PM
|
Permanent Service | 9/23/2003 | 9/23/2003 | 9/23/2003 | P | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|
Electrical Rough-In | 9/15/2003 | 9/15/2003 | 9/15/2003 | P | FAIL |
Jack Frank
|
|
|
ERIC; Phone #: ###-#### Internet Inspection Request from: Marc Lileks needs required spacing between conduit entries jbox basement 314.28(A)(2) note when p/s is ready check for bonding means called left message 9/15/2003 3:49:39 PM
|
Final | 9/10/2003 | 9/11/2003 | 9/11/2003 | A | CANC |
Jack Frank
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Annette Moore r/i ok
314.28 jbox by chase in basement, remove GEC from jbox, 9/11/2003 9:49:52 AM
|
Electrical Rough-In | 9/11/2003 | 9/11/2003 | 9/11/2003 | A | PART |
Jack Frank
|
|
|
upstairs ok see notes canceled final request
|
Rough-In Permanent Service | 9/9/2003 | 9/9/2003 | 9/9/2003 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/9/2003 at 7:26:45 AM. Contact: ###-####. cor. posted called 300.4 (A)(1)&(D), ID grd to rebar, 330.30(C) strap MC within 12 inches of boxes, 110.3(B) use staples as listed 9/9/2003 1:10:23 PM
|
Application received | | | 8/27/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 8/27/2003 | | DONE |
|
|
|
|