Final | 11/17/2003 | 11/18/2003 | 11/18/2003 | A | PASS |
Jack Frank
|
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 11/18/2003 12:49:58 PM
|
DOC - Permit Finaled | 11/18/2003 | 11/18/2003 | 11/18/2003 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 11/18/2003 12:50:03 PM
|
Final | 11/14/2003 | 11/17/2003 | 11/17/2003 | A | FAIL |
Jack Frank
|
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes line and load gfci met owner 11/17/2003 10:49:56 AM
|
Final | 11/12/2003 | 11/13/2003 | 11/13/2003 | A | FAIL |
Pat Lass
|
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
210.8 11/13/2003 11:22:56 AM
|
Electrical Rough-In | 10/3/2003 | 10/6/2003 | 10/6/2003 | A | PASS |
Jack Frank
|
|
|
ron///elcetrod; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ok for concrete 10/6/2003 8:22:37 AM
|
Electrical Rough-In | 9/29/2003 | 9/30/2003 | 9/30/2003 | A | FAIL |
Jack Frank
|
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called left message needs concrete encased electrode installed, 334.15 protect romex , 250.32(B)(1) remove bond screw 9/30/2003 10:20:00 AM
|
Electrical Rough-In | 9/29/2003 | 9/29/2003 | 9/29/2003 | P | NH |
Jack Frank
|
|
|
ron ; Phone #: ###-#### Internet Inspection Request from: Annette Moore notice posted called left message 9/29/2003 3:31:20 PM
|
Application received | | | 9/2/2003 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/2/2003 | | DONE |
|
|
|
|