Third Notice ELE | 2/9/2004 | 2/9/2004 | 2/25/2004 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 1/22/2004 | 1/22/2004 | 2/9/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 12/30/2003 | 1/22/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 12/30/2003 | 12/30/2003 | 12/30/2003 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 12/30/2003 10:19:48 AM
|
ELE-Aging Inspection | 12/30/2003 | 12/30/2003 | 12/30/2003 | | DONE |
Jack Frank
|
|
|
done 10-22-03 by Bill 12/30/2003 10:19:42 AM
|
Final | 10/22/2003 | 10/22/2003 | 10/22/2003 | P | PASS |
William E Thomas
|
|
|
gary- ###-#### -re-insp
final ok per 432 10/22/2003 1:28:26 PM
|
Final | 10/17/2003 | 10/17/2003 | 10/17/2003 | P | FAIL |
Jack Frank
|
|
|
###-####--gary cor. posted called wiremold shall be installed to meet386.100 , 250.148 grd all boxes, 110.12(A) seal all unused openings, 300.14 needs 6" free length conductor at all outets and j boxes, use approved fittings for plug mold not duct tape, no violations to be retained isolate grds and neutrals at sub panel, shall not ID 6 or samller neutral, 10/17/2003 1:59:43 PM
|
Application received | | | 9/12/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 9/12/2003 | | DONE |
|
|
|
|