Final | 3/17/2005 | 3/18/2005 | 3/18/2005 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/17/2005 at 8:56:36 PM. Contact: ###-####. job is a mess owner had someone else do work permit for p/s and 2rooms he rewired almost all of the house, kit wiring not right , bath 20 amp has bedrm and garage on it wall spacing open grds, wires just twisted together in boxes screws in plastic boxes wired cover and no inspection 3/18/2005 3:27:15 PM
|
ELE-Request for Extension | 8/11/2004 | 8/11/2004 | 8/11/2004 | P | DONE |
Jack Frank
|
|
|
Jim; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 8/11/2004 9:44:42 AM
|
PostCard Mailed | | | 8/4/2004 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
Permanent Service | 10/23/2003 | 10/23/2003 | 10/23/2003 | P | PASS |
William E Thomas
|
|
|
ceiling grid- mark--re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
p/s o/h reconnect ok per 432 10/23/2003 1:18:25 PM
|
Permanent Service | 10/22/2003 | 10/22/2003 | 10/22/2003 | P | FAIL |
William E Thomas
|
|
|
hahn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
per BCC two ground rods needed, NEC 250.53 requires 6' spaceing 10/22/2003 2:01:02 PM
|
Issue PAID IN FULL permit | | | 10/10/2003 | | DONE |
|
|
|
|
Application received | | | 10/8/2003 | | |
|
|
|
|