Final | 1/20/2004 | 1/20/2004 | 1/20/2004 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/20/2004 at 8:34:59 AM. Contact: ###-####. ok no card 1/20/2004 12:39:38 PM
|
DOC - Permit Finaled | 1/20/2004 | 1/20/2004 | 1/20/2004 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 1/20/2004 12:39:44 PM
|
Electrical Rough-In | 11/13/2003 | 11/13/2003 | 11/13/2003 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/13/2003 at 8:33:14 AM. Contact: ###-####. walls ok 11/13/2003 1:45:05 PM
|
Electrical Rough-In | 11/12/2003 | 11/12/2003 | 11/12/2003 | P | FAIL |
Jack Frank
|
|
|
###-#### Jim cor. posted called 300.4 nail plates and 11/4" , 250.24(A)(5) isolate geds and neuts at sub panel, 300.10 loose set screws, 110.12(A) seal unused KOs, 300.11(B)&(C) shall not support cables from raceways or cables, 10.3 use approved means to secure cables and raceways no tie wire allowed 11/12/2003 2:02:41 PM
|
Issue permit | | | 11/12/2003 | | DONE |
|
|
|
|
Application received | | | 11/12/2003 | | |
|
|
|
|