Second Notice ELE | 12/19/2003 | 12/19/2003 | 1/13/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 11/26/2003 | 12/19/2003 | | DONE |
|
|
|
|
DOC - Permit Finaled | 11/26/2003 | 11/26/2003 | 11/26/2003 | A | PASS |
Mike Kinnear
|
|
|
Finaled by inspector at 11/26/2003 8:22:45 AM
|
Final | 11/25/2003 | 11/26/2003 | 11/26/2003 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 11/25/2003 at 11:26:28 AM. ok final 11/26/2003 8:22:43 AM
|
Rough-In Permanent Service | 11/17/2003 | 11/17/2003 | 11/17/2003 | P | PASS |
Jack Frank
|
|
|
Brad; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes r/i ok
p/s u/g new ok 11/17/2003 3:33:32 PM
|
Rough-In Permanent Service | 11/13/2003 | 11/14/2003 | 11/14/2003 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called no response phone number not in service,, 300.4 (A)(1)&(D), 352.30 (A) strap 2" pvc, 250.24(A)(5) isolate grds and neut at sub panel, 250.122 install equip grd to sub panel, 250.64 grd to electrodes for new p/s 11/14/2003 2:41:25 PM
|
Application received | | | 11/13/2003 | | |
|
|
|
|
Issue permit | | | 11/13/2003 | | DONE |
|
|
|
|