Second Notice ELE | 1/22/2004 | 1/22/2004 | 2/4/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 12/22/2003 | 1/22/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 12/22/2003 | 12/22/2003 | 12/22/2003 | P | PASS |
Joe Ray
|
|
|
Finaled by inspector at 12/22/2003 2:34:58 PM
|
Final | 12/22/2003 | 12/22/2003 | 12/22/2003 | P | PASS |
Joe Ray
|
|
|
George; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
Final | 12/19/2003 | 12/19/2003 | 12/19/2003 | P | FAIL |
Jack Frank
|
|
|
Georg; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes cor. not made still needs to install boxes for unused mc cable with open wires called 12/19/2003 2:49:44 PM
|
Final | 12/18/2003 | 12/18/2003 | 12/18/2003 | P | FAIL |
Jack Frank
|
|
|
George; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes cor. posted called 300.11 install and ID cabled support wires, 604.6 secure manufactured wiring system, 300.15 terminate all unused cables in boxes 12/18/2003 3:03:11 PM
|
Electrical Rough-In | 12/2/2003 | 12/2/2003 | 12/2/2003 | P | PART |
William E Thomas
|
|
|
george- ###-####
walls only, no cieling cover for drop cieling in the affected areas. 12/2/2003 4:31:04 PM
|
Application received | | | 12/2/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 12/2/2003 | | DONE |
|
|
|
|