Final | 1/12/2004 | 1/12/2004 | 1/12/2004 | P | PASS |
Jack Frank
|
|
|
###-#### steve please call for access ok 1/12/2004 1:29:10 PM
|
DOC - Permit Finaled | 1/12/2004 | 1/12/2004 | 1/12/2004 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 1/12/2004 1:29:15 PM
|
Electrical Rough-In | 12/24/2003 | 12/24/2003 | 12/24/2003 | P | PASS |
Jack Frank
|
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 12/24/2003 12:22:19 PM
|
Electrical Rough-In | 12/15/2003 | 12/15/2003 | 12/15/2003 | P | FAIL |
Jack Frank
|
|
|
steve--call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called no response 12/15/2003 12:25:24 PM called left message 12/15/2003 3:28:54 PM cor. posted met owner 250.148 ligh box outside, 300.4(A)(1)&(D), 250.32 isolate grds and neuts at shop, 250.52,53 install 2 grd rods at shop, 334.15 protect horizontal runs of romex, 110.3(B) use manufactures breakers only, expose 4 locations of u/g covered before inspection staple romex within 8" of boxes, all makeup shall be complete 12/15/2003 5:07:46 PM
|
Application received | | | 12/12/2003 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/12/2003 | | DONE |
|
|
|
|