Second Notice ELE | 3/17/2004 | 3/17/2004 | 3/19/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 2/17/2004 | 3/17/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 2/17/2004 | 2/17/2004 | 2/17/2004 | P | PASS |
Joe Ray
|
|
|
Finaled by inspector at 2/17/2004 3:02:58 PM
|
Final | 2/17/2004 | 2/17/2004 | 2/17/2004 | P | PASS |
Joe Ray
|
|
|
Final Reinspect - Thank You; Phone #: ###-#### Internet Inspection Request from: Dawn Moore
|
Final | 2/12/2004 | 2/13/2004 | 2/13/2004 | A | FAIL |
Jack Frank
|
|
|
FINAL REINSPECT - THANK YOU; Phone #: ###-#### Internet Inspection Request from: Dawn Moore correction not made 314.20 boxes shall be flush with combustible finish called 2/13/2004 9:12:00 AM
|
Final | 2/12/2004 | 2/12/2004 | 2/12/2004 | P | FAIL |
Joe Ray
|
|
|
final inspection for Parkview Apartments Recreation Room; Phone #: ###-#### Internet Inspection Request from: Dawn Moore 314-21 boxes shall be flush with combustable material 2/12/2004 2:12:40 PM
|
Electrical Rough-In | 1/13/2004 | 1/14/2004 | 1/14/2004 | A | PASS |
Jack Frank
|
|
|
ready for reinspect of rough-in; Phone #: ###-#### Internet Inspection Request from: Dawn Moore ok 1/14/2004 8:54:12 AM
|
Electrical Rough-In | 1/13/2004 | 1/13/2004 | 1/13/2004 | P | NR |
Mike Kinnear
|
|
|
dawn; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie conf with electrician need #6 ground for range equip bond jumper in panal & new box for heater stat. mc cable for heater (bathrm) 1/13/2004 2:05:39 PM
|
Application received | | | 1/13/2004 | | |
|
|
|
|
Issue permit | | | 1/13/2004 | | DONE |
|
|
|
|