Second Notice ELE | 6/21/2004 | 6/21/2004 | 6/21/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 5/28/2004 | 6/21/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 5/28/2004 | 5/28/2004 | 5/28/2004 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 5/28/2004 8:30:27 AM
|
Final | 5/28/2004 | 5/28/2004 | 5/28/2004 | A | PASS |
Jack Frank
|
|
|
ok
|
Rough-In Permanent Service | 5/10/2004 | 5/11/2004 | 5/11/2004 | A | FAIL |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 5/10/2004 at 11:49:55 AM. Contact: ###-####.
no burial inspection 5/11/2004 9:07:24 AM
|
Rough-In Permanent Service | 5/11/2004 | 5/11/2004 | 5/11/2004 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/11/2004 at 9:20:13 AM. Contact: ###-####. cor. posted called 300.5, 250.24 terminate GEC to neutral bus, 110.9, 110.10 p/s shall be rated for fault and short circuit current levels p/s is next to ID power x former
needs permit for his work he is using sign contractors permit now 5/11/2004 12:47:04 PM
|
Application received | | | 3/11/2004 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 3/11/2004 | | |
|
|
|
|