Second Notice ELE | 6/21/2004 | 6/21/2004 | 7/6/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 6/2/2004 | 6/21/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 6/2/2004 | 6/2/2004 | 6/2/2004 | P | PASS |
Pat Lass
|
|
|
Finaled by inspector at 6/2/2004 2:06:49 PM
|
Conference | 6/2/2004 | 6/2/2004 | 6/2/2004 | P | PASS |
Pat Lass
|
|
|
We are requesting a conference with the inspector and the owner. If possible call 30min before so that we can get the correct people at the job site. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer
|
Final | 5/26/2004 | 5/27/2004 | 5/27/2004 | P | PART |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer
signed T/O
discussed show window receps and was told that no ads would be in windows.
cords are not permited as subistute for hard wiring on outside booths. 5/27/2004 3:39:05 PM
|
Electrical Rough-In | 5/21/2004 | 5/24/2004 | 5/24/2004 | A | PASS |
Pat Lass
|
|
|
Ceiling inspection in the kitchen. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer
|
Electrical Rough-In | 5/18/2004 | 5/19/2004 | 5/19/2004 | A | PART |
Pat Lass
|
|
|
Ceiling inspection in the Kitchen. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer
ok 5/19/2004 9:05:17 AM
|
Permanent Service | 4/27/2004 | 4/27/2004 | 4/27/2004 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer
P/S O/h R Ok 4/27/2004 10:13:28 AM
|
Permanent Service | 4/20/2004 | 4/21/2004 | 4/21/2004 | A | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer
could not locate SUSE lable or main bonding jumper 4/21/2004 9:55:23 AM
|
Electrical Rough-In | 4/19/2004 | 4/20/2004 | 4/20/2004 | A | PART |
Pat Lass
|
|
|
Underground inspection. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer
U/G Inside in front and outside ok 4/20/2004 10:36:25 AM
|
Electrical Rough-In | 4/6/2004 | 4/8/2004 | 4/8/2004 | P | PART |
Pat Lass
|
|
|
###-#### This is for a cover inspection. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer 4/8/2004 7:39:52 AM
walls and hard lid ok 4/8/2004 2:52:35 PM
|
Electrical Rough-In | 3/17/2004 | 3/18/2004 | 3/18/2004 | P | PART |
William E Thomas
|
|
|
This is an under-ground service inspections request. Chris Wright is the journeyman on the job: ###-####. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer 3/18/2004 1:02:33 PM
underground conduits from outside to inside,east side of building ok to cover 3/18/2004 1:25:14 PM
|
Application received | | | 3/11/2004 | | |
|
|
|
|
Issue & PRINT permit | | | 3/11/2004 | | DONE |
|
|
|
|