Permanent Service | 4/5/2004 | 4/5/2004 | 4/5/2004 | P | PASS |
Jack Frank
|
|
|
re inspection of service.; Phone #: ###-#### Internet Inspection Request from: Andy Rose
p/s o/h rec. ok 4/5/2004 12:53:10 PM
|
DOC - Permit Finaled | 4/5/2004 | 4/5/2004 | 4/5/2004 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 4/5/2004 12:53:14 PM
|
Permanent Service | 3/31/2004 | 3/31/2004 | 3/31/2004 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Andy Rose cor. posted called 110.3(B) and 314.3 exception (1) shall provide bond bushing on metallic conduits in nonmetallic box , do not use old grd rod it is to close to new ones 3/31/2004 2:31:50 PM
|
Application received | | | 3/29/2004 | | |
|
|
|
|
Issue & PRINT permit | | | 3/29/2004 | | |
|
|
|
|