Second Notice ELE | 4/29/2004 | 4/29/2004 | 4/29/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 4/19/2004 | 4/29/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 4/19/2004 | 4/19/2004 | 4/19/2004 | P | PASS |
Pat Lass
|
|
|
Finaled by inspector at 4/19/2004 1:58:24 PM
|
Temporary Service | 4/16/2004 | 4/19/2004 | 4/19/2004 | A | PASS |
Pat Lass
|
|
|
rich; Phone #: ###-#### Internet Inspection Request from: Annette Moore
T/S O/H Ok 4/19/2004 1:58:22 PM
|
Temporary Service | 4/12/2004 | 4/13/2004 | 4/13/2004 | A | FAIL |
Pat Lass
|
|
|
temp pole on north west corner of lot by petra job trailer; Phone #: ###-#### Internet Inspection Request from: Rich Rice
GFCi protect 240v receps.
ground job trailer.
drive ground rods flush.
ground wireway/gutter.
LFMC requires grounding wire to be installed and bond bushing between meter and main. 4/13/2004 9:20:08 AM
|
Application received | | | 4/8/2004 | | |
|
|
|
|
Issue & PRINT permit | | | 4/8/2004 | | DONE |
|
|
|
|