Third Notice ELE | 5/19/2004 | 5/19/2004 | 1/18/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 4/28/2004 | 4/28/2004 | 5/19/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 4/16/2004 | 4/28/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 4/16/2004 | 4/16/2004 | 4/16/2004 | P | PASS |
Pat Lass
|
|
|
Finaled by inspector at 4/16/2004 1:47:58 PM
|
Permanent Service | 4/16/2004 | 4/16/2004 | 4/16/2004 | P | PASS |
Pat Lass
|
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
P/S O/H N Ok 4/16/2004 1:47:56 PM
|
Permanent Service | 4/14/2004 | 4/15/2004 | 4/15/2004 | A | FAIL |
Jack Frank
|
|
|
GLENN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
cor. posted called 200.6 shall not ID #6 or smaller neutral, 250.28, 110.3(B) shall bond p/s enclosure with manufactures listed means 4/15/2004 9:49:39 AM
|
Permanent Service | 4/13/2004 | 4/13/2004 | 4/13/2004 | P | FAIL |
Pat Lass
|
|
|
###-#### glenn
cannot have 2 services to a building
conductors for street lights cannot enter the building 4/13/2004 3:36:53 PM
|
Issue permit | | | 4/13/2004 | | DONE |
|
|
|
|
Application received | | | 4/13/2004 | | |
|
|
|
|