Final | 6/17/2004 | 6/17/2004 | 6/17/2004 | A | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa
|
DOC - Permit Finaled | 6/17/2004 | 6/17/2004 | 6/17/2004 | A | PASS |
Pat Lass
|
|
|
Finaled by inspector at 6/17/2004 11:13:40 AM
|
Final | 6/14/2004 | 6/15/2004 | 6/15/2004 | A | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa
210.52 Dwelling Unit Receptacle Outlets.
(A) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed in accordance with the general provisions specified in 210.52(A)(1) through (A)(3).
Receptacle outlet required within 6' of doorway opening by window seat.
410.8 Luminaires (Fixtures) in Clothes Closets.
(C) Luminaire (Fixture) Types Not Permitted. Incandescent luminaires (fixtures) with open or partially enclosed lamps and pendant luminaires (fixtures) or lampholders shall not be permitted.
The address is still wrong on the permit.
6/15/2004 9:47:28 AM
|
Electrical Rough-In | 4/14/2004 | 4/14/2004 | 4/14/2004 | P | PASS |
Pat Lass
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Electrical Rough-In | 4/13/2004 | 4/13/2004 | 4/13/2004 | P | FAIL |
Pat Lass
|
|
|
###-#### james
4 violations in one box.
box overfill.
screws inside box.
parallel romex not protected within 1 1/4 in.
romex not supported within 8 in. in several places.
address is west north mountain not north 4/13/2004 1:50:31 PM
|
Issue permit | | | 4/13/2004 | | DONE |
|
|
|
|
Application received | | | 4/13/2004 | | |
|
|
|
|