Second Notice ELE | 7/7/2004 | 7/7/2004 | 7/8/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 6/17/2004 | 7/7/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 6/17/2004 | 6/17/2004 | 6/17/2004 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 6/17/2004 3:39:54 PM
|
Final | 6/17/2004 | 6/17/2004 | 6/17/2004 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/17/2004 at 10:02:49 AM. Contact: ###-####. ok 6/17/2004 3:39:51 PM
|
Rough-In Permanent Service | 4/29/2004 | 4/30/2004 | 4/30/2004 | A | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 4/29/2004 at 3:05:01 PM. Contact: ###-####.
rough ok to cover 4/30/2004 11:16:58 AM
|
Rough-In Permanent Service | 4/29/2004 | 4/29/2004 | 4/29/2004 | P | PART |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 4/29/2004 at 7:44:32 AM. Contact: ###-####.
330.30, 362.30, 250.24 isolate neutral and grounds in sub panel. no feeders have been pulled into the service, and the sub panels also.
p/s u/g n ok 4/29/2004 2:18:15 PM
|
Application received | | | 4/22/2004 | | |
|
|
|
|
Issue permit | | | 4/22/2004 | | DONE |
|
|
|
|