Information based on query as of Friday, July 19, 2024.
Permit Information
Permit NumberELE04-01519
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 390 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReview 
Description
generator and transfer switch install $130,000
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice Sent 10/28/200411/2/2004 DONE
This permit finaled on the web by Deb McCoy
DOC - Permit Finaled10/28/200410/28/200410/28/2004PPASS
DetailsMike Kinnear
Finaled by inspector at 10/28/2004 2:53:24 PM
Final10/27/200410/28/200410/28/2004APASS
DetailsMike Kinnear
CONTACT: PHIL BASSICK - RE-INSPECTION 9:00 AM PLEASE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok final as per 324 10/28/2004 2:53:19 PM
Electrical Rough-In10/18/200410/18/200410/18/2004APASS
DetailsMike Kinnear
conf with electrical eng.
Final10/18/200410/18/200410/18/2004PPART
DetailsMike Kinnear
324 & 412 conf with eclectrial eng.
Final10/14/200410/14/200410/14/2004PFAIL
DetailsMike Kinnear
correction BCO 4-05-33(A) listing & lable
Final10/8/200410/12/200410/12/2004PCANC
DetailsMike Kinnear
resched for 10/11/04 pm 412 10/11/2004 9:53:41 AM
Final10/11/200410/15/200410/11/2004ACANC
DetailsMike Kinnear
Final10/11/200410/11/200410/11/2004PCANC
DetailsMike Kinnear
resched for 10/15/ 04 am t/w tri state & factory they to get proper label by then 10/11/2004 5:29:58 PM
Final10/6/200410/8/200410/8/2004PFAIL
DetailsMike Kinnear
factory called they have not received anything from ul yet. i advise we are going to start procedures to shut off power to building. 10/8/2004 1:42:39 PM
Final9/29/200410/6/200410/6/2004PNR
DetailsMike Kinnear
t/w phil they have to get us information for ul labling or we will have to start prosess to shut power off at the building 10/6/2004 2:46:52 PM
Final9/28/20049/29/20049/29/2004PNR
DetailsMike Kinnear
t/w phil factory forgot to put stickers on equipment -- told phil they needed UL rep to put them on equip. 9/29/2004 2:08:53 PM
Final9/27/20049/28/20049/28/2004PFAIL
DetailsMike Kinnear
phil called he check with factory & advise electrical eng called for factory will check out & advise 9/28/2004 12:29:51 PM
Final9/27/20049/27/20049/27/2004PFAIL
DetailsMike Kinnear
CONTACT: CHRIS CARMINE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy fail no sticker for service rated equipment. nec 110.3 9/27/2004 5:23:49 PM
Electrical Rough-In9/21/20049/21/20049/21/2004PPART
DetailsMike Kinnear
CONTACT: CHRIS CARMINE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy p/s u/g reconnect ok --- note need to look at grounding electrode & isolated neut. in switches 9/21/2004 3:05:51 PM
Electrical Rough-In8/30/20048/31/20048/31/2004APART
DetailsWilliam E Thomas
contact: Chris Carmine - underground inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
underground burial depth ok 8/31/2004 10:22:18 AM
ELE-Aging Inspection8/2/20048/2/20048/2/2004 NR
DetailsMike Kinnear
suc 8/3/2004 7:40:14 AM
Conference5/24/20045/24/20045/24/2004PPASS
DetailsMike Kinnear
###-#### phil please call for access conf with phil ok 5/24/2004 1:18:55 PM
Issue permit  5/24/2004 DONE
Application received  5/24/2004