Second Notice ELE | 7/23/2004 | 7/23/2004 | 7/26/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 7/1/2004 | 7/23/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 7/1/2004 | 7/1/2004 | 7/1/2004 | A | PASS |
Joe Ray
|
|
|
Finaled by inspector at 7/1/2004 10:58:41 AM
|
Final | 6/30/2004 | 7/1/2004 | 7/1/2004 | A | PASS |
Joe Ray
|
|
|
jay; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles, CHANGED INSP TO 7/1/04 PER JIM SCHMER. ADH.
|
Final | 6/30/2004 | 6/30/2004 | 6/30/2004 | P | CANC |
William E Thomas
|
|
|
|
Final | 6/30/2004 | 6/30/2004 | 6/30/2004 | P | DONE |
William E Thomas
|
|
|
stop work issued until corrections made, per jim schmeer
|
Final | 6/28/2004 | 6/28/2004 | 6/28/2004 | P | FAIL |
Joe Ray
|
|
|
jay; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 314.23 supports of boxes/400- fixed wiring not permitted for cords/110-3 equipment listings/344-30 supports for condiut 6/28/2004 12:37:54 PM
|
Electrical Rough-In | 6/21/2004 | 6/22/2004 | 6/22/2004 | A | PASS |
Joe Ray
|
|
|
Jay; Phone #: ###-#### ceiling R/IInternet Inspection Request from: Aimee Hughes ceiling ok 6/22/2004 11:27:19 AM
|
Electrical Rough-In | 6/18/2004 | 6/18/2004 | 6/18/2004 | A | FAIL |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 6/18/2004 at 7:17:05 AM. Contact: ###-####.
fail cieling inspection, 330.30 mc supports, 800.52B abandoned communication cable 6/18/2004 10:23:58 AM
|
Electrical Rough-In | 6/7/2004 | 6/8/2004 | 6/8/2004 | P | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 6/7/2004 at 1:31:48 PM. Contact: ###-####. walls ok 6/8/2004 4:30:32 PM
|
Application received | | | 6/7/2004 | | |
|
|
|
|
Issue permit | | | 6/7/2004 | | DONE |
|
|
|
|