(F) Reprint permit | | | 11/13/2006 | | |
|
|
|
|
Final | 9/19/2006 | 9/20/2006 | 9/20/2006 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/19/2006 at 4:07:05 PM. Contact: ###-####. ok
|
Final | 9/14/2006 | 9/15/2006 | 9/15/2006 | A | FAIL |
Jack Frank
|
|
|
mike - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. fee due see notes fee due
|
Reinspection Fee (no hold) | 9/15/2006 | 9/15/2006 | 9/15/2006 | A | DONE |
Jack Frank
|
|
|
mike - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. fee due met contr. 210.52(B) shall provide 20 amp SABC for island counter, 314.16 box fill island , 410.8 clearence MB colset fixture
|
Electrical Rough-In | 8/22/2006 | 8/23/2006 | 8/23/2006 | P | PASS |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley storage basement ok
|
Final | 8/2/2006 | 8/3/2006 | 8/3/2006 | P | NR |
Jack Frank
|
|
|
please call prior to inspection so it can be opened ###-#### Mike see added r/i
|
Electrical Rough-In | 8/3/2006 | 8/3/2006 | 8/3/2006 | P | PART |
Jack Frank
|
|
|
please call prior to inspection so it can be opened ###-#### Mike ok corr. made, bath rm ok, island in kit needs too meet requirements of 210.52 (C)(1) 2ft 4ft rule gave cover contractor will corr. I will check it at time of final
|
Rough-In Permanent Service | 1/20/2005 | 1/21/2005 | 1/21/2005 | P | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--re-insp Met with contractor and he has done the corrections, except he is going to put a ground bushing in the service panel for the recpt since he used reducing washers. ok to cover closet walls and I put a sticker on the panel, even though it has a working meter. 1/21/2005 12:48:50 PM
|
Rough-In Permanent Service | 12/27/2004 | 12/28/2004 | 12/28/2004 | A | FAIL |
Jack Frank
|
|
|
please call for access mike ###-#### cor. posted met contractor 250.52(A)(1) grd to water, 110.26(F)(2) clearence for service,,250.8 no SMS, shall not ID 6 or smaller grds and neutrals , bond bushing for RE washers, use manufactures equip grd bus, job not ready 12/28/2004 9:19:37 AM
|
(F) Reprint permit | | | 12/27/2004 | | |
|
|
|
|
Application received | | | 6/21/2004 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/21/2004 | | DONE |
|
|
|
|