Permanent Service | 1/6/2005 | 1/6/2005 | 1/6/2005 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/6/2005 at 9:16:23 AM. Contact: ###-####. r/i ok
p/s o/h rec. ok 1/6/2005 1:16:30 PM
|
Permanent Service | 1/5/2005 | 1/5/2005 | 1/5/2005 | P | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/5/2005 at 8:23:04 AM. Contact: ###-####. see added r/i for concrete encased electrode 1/5/2005 1:20:01 PM
|
Electrical Rough-In | 1/5/2005 | 1/5/2005 | 1/5/2005 | P | PART |
Jack Frank
|
|
|
electrode ok for concrete cover
|
Electrical Rough-In | 12/30/2004 | 12/30/2004 | 12/30/2004 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/30/2004 at 6:46:03 AM. cor. made for r/i ok 12/30/2004 9:41:11 AM
|
Electrical Rough-In | 12/20/2004 | 12/20/2004 | 12/20/2004 | P | FAIL |
Jack Frank
|
|
|
amy or josh; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. posted met owner 300.4, 200.6, shall ID,or use white as phase, 314.20 outside boxes flush, 250.24 install bond screw, 250.52(A)(1),104(A)(1) grd or bond water pipe, 210.52(A) outlet spacing, 210.11(C) laundry circuit, 210.52(D) outlet within 3ft of sink,250.140 needs insulated neutral to range, shall install concrete encased electrode,314.17(C) replace 2gang box broken clamp,310.15 derate conductors in 2" pvc,230.28 support p/s mast 12/20/2004 5:03:15 PM
|
Issue PAID IN FULL permit | | | 6/30/2004 | | DONE |
|
|
|
|
Application received | | | 6/29/2004 | | |
|
|
|
|