Second Notice ELE | 9/8/2004 | 9/8/2004 | 9/14/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 8/20/2004 | 9/8/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 8/20/2004 | 8/20/2004 | 8/20/2004 | A | PASS |
Mike Kinnear
|
|
|
Finaled by inspector at 8/20/2004 9:31:54 AM
|
Final | 8/19/2004 | 8/20/2004 | 8/20/2004 | A | PASS |
Mike Kinnear
|
|
|
donna; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok final 8/20/2004 9:31:52 AM
|
Final | 8/16/2004 | 8/16/2004 | 8/16/2004 | P | FAIL |
Mike Kinnear
|
|
|
WARREN; Phone #: ###-#### Internet Inspection Request from: Annette Moore corrections nectable wire size for 225amp shall be 4/0, nec250.66 grounding electroode conductor size for 4/0 shall be 2 cu bc reuires 2 ground rods 6ft or more apart . 8/16/2004 3:33:45 PM
|
Electrical Rough-In | 7/7/2004 | 7/8/2004 | 7/8/2004 | A | PART |
Mike Kinnear
|
|
|
Trench inspection please////Warren ###-#### ok cover under ground conduit 7/8/2004 9:18:00 AM
|
Application received | | | 7/1/2004 | | |
|
|
|
|
Issue permit | | | 7/1/2004 | | DONE |
|
|
|
|