Permanent Service | 7/21/2004 | 7/21/2004 | 7/21/2004 | A | PASS |
Jack Frank
|
|
|
p/s o/h rec. ok
|
DOC - Permit Finaled | 7/21/2004 | 7/21/2004 | 7/21/2004 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 7/21/2004 8:41:25 AM
|
Final | 7/20/2004 | 7/21/2004 | 7/21/2004 | A | PASS |
Jack Frank
|
|
|
charles; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 7/21/2004 8:40:44 AM
|
Permanent Service | 7/16/2004 | 7/19/2004 | 7/19/2004 | A | FAIL |
Jack Frank
|
|
|
###-#### charles cor. posted needs 2 grd rods , grd at 5 ft where water enters, 10 clearence to drip loop from back porch, remove tree stump from below p/s, shall not split large wires into small sections to fit under lugs, W H needs #10 wire and 30 amps address sub panel some violations if ? call JF 7/19/2004 10:00:56 AM
|
Issue PAID IN FULL permit | | | 7/16/2004 | | DONE |
|
|
|
|
Application received | | | 7/16/2004 | | |
|
|
|
|