Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberELE04-02374
StatusFinaled
Name SMART ELECTRIC
Site Address 1312 N 20TH ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/24/201312/24/201312/24/2013PPASS
DetailsRock A. Hudson
Corrections completed on permit ele13-03542. Final ok
Final12/18/201312/19/201312/19/2013AFAIL
DetailsRock A. Hudson
Before 11, call for access - April Phone #: ###-#### BCC-4-05-23 Unlawful to conceal. Basement wiring covered with out first being inspected.
210.52- Basement dows not have minimum reqired receptical outlet installed measured along floor line.
314.25- All boxes shall be complete with covers. Furnace disconnect.
422.30- A disconnecting means shall be provided for water heater.
110.3- Family room receptical outlet not working.
210.8- Back outdoor receptical shall have GFCI protection.
406.3(D)- Grounding type recepticals installed on non-grounded circuits shall have GFCI protection.
Change Status to I  12/18/2013 DONE
DetailsChristina Prado
Per Bob Archibald 12-13-13 - ok to reopen permits with 1/2 orig fee to get final inspections
(F) Reprint permit  12/18/2013 DONE
Electrical Rough-In8/19/20048/20/20048/20/2004APART
DetailsWilliam E Thomas
clyde; Phone #: ###-#### Internet Inspection Request from: Annette Moore
ri ok mainfloor and upstairs.
no cover allowes on basement 8/20/2004 9:04:47 AM
Rough-In Permanent Service8/5/20048/6/20048/6/2004PFAIL
DetailsPat Lass
###-#### clyde
ground service to metal water pipe.

250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes.
A connection shall be made between the one or more equipment grounding conductors and a box
Upstairs and main floor.
314.17 Conductors Entering Boxes, Conduit Bodies, or Fittings.
Conductors entering boxes, conduit bodies, or fittings shall be protected from abrasion and shall comply with 314.17(A) through (D).
At panel
8/6/2004 2:12:31 PM 8/6/2004 2:21:11 PM
Permanent Service8/6/20048/6/20048/6/2004PPART
DetailsPat Lass
P/S O/H R Ok
to transfer power to new location
Application received  8/5/2004  
Issue permit  8/5/2004 DONE