Permit Information
Permit NumberELE04-02543
StatusFinaled
Name VANZANDT ELECTRIC
Site Address 1305 E WARM SPRINGS AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/1/20053/1/20053/1/2005PPASS
DetailsPat Lass
###-####. Scheduled by a contractor via Hello! on 3/1/2005 at 11:22:12 AM. Contact: ###-####. 3/1/2005 11:47:18 AM
DOC - Permit Finaled3/1/20053/1/20053/1/2005PPASS
DetailsPat Lass
Finaled by inspector at 3/1/2005 2:24:35 PM
Conference2/15/20052/16/20052/16/2005APART
DetailsPat Lass
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice
covered grounding and gfci and continuity of raceway and white used as ungrounded conductor 2/16/2005 9:39:31 AM
Final2/15/20052/15/20052/15/2005PNR
DetailsPat Lass
###-####. Scheduled by a contractor via Hello! on 2/15/2005 at 10:12:24 AM. Contact: ###-####. 2/15/2005 11:37:46 AM
must have conf with contractor 2/15/2005 2:35:16 PM
Final2/11/20052/11/20052/11/2005PFAIL
DetailsWilliam E Thomas
Brett-call first; Phone #: ###-#### Internet Inspection Request from: Jan Rice
corrections still not made, elevator equipment signage,recedpticle, light, protection of low-voltage wiring with bushings, water grounding- where does it tie to the main system? 2/11/2005 3:00:24 PM
Final1/27/20051/28/20051/28/2005AFAIL
DetailsJack Frank
please call prior to inspection so he can meet ya there//brett; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called 210.8 gfci for unfinished basement recepts, 310.15 derate wires in pvc at p/s, also all pvc fittings shall be made up tightand LB covers and gaskets, 250.52(A)(1) terminate GEC from water to p/s, 620.52 install labels noting 2 power sources,and warning signs, 250.24(A)(5) isolate all neutrals and grds at all sub gear check elevator disconnect also,, note elevator contractor needs permit, is he licensed in Idaho?, all elevator wiring shall meet NEC required outlets for equip rm connectors for flex, cables, and low voltage shall have proper voltage rating when install with high voltage in cabinet 1/28/2005 1:17:59 PM
Electrical Rough-In8/18/20048/19/20048/19/2004APART
DetailsWilliam E Thomas
###-#### - john
ri ok
did not see new service 8/19/2004 10:01:47 AM
Issue permit  8/18/2004 DONE
Application received  8/18/2004