Final | 10/25/2004 | 10/26/2004 | 10/26/2004 | A | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 10/25/2004 at 1:32:25 PM. Contact: ###-####.
|
DOC - Permit Finaled | 10/26/2004 | 10/26/2004 | 10/26/2004 | A | PASS |
William E Thomas
|
|
|
Finaled by inspector at 10/26/2004 10:05:34 AM
|
Final | 10/15/2004 | 10/15/2004 | 10/15/2004 | P | FAIL |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 10/15/2004 at 8:01:31 AM. Contact: ###-####.
680.23F3-no gfci protected conductors to occupy conduit space with non gfci protected conductors
680.12-disconnect for all utilization equipment to be installed within sight of equipment
680.26-pool equipment bonding conductor shall not be connected to equipment grounding conductors
680.26B3-all metal components shall be bonded
* the water level needs to be lowered so that the potting compound can be inspected. 10/15/2004 4:21:19 PM 10/15/2004 4:21:33 PM
|
Electrical Rough-In | 10/6/2004 | 10/6/2004 | 10/6/2004 | P | PASS |
Pat Lass
|
|
|
###-#### - todd Note: Pool Bonding
|
Application received | | | 10/5/2004 | | |
|
|
|
|
Issue & PRINT permit | | | 10/5/2004 | | DONE |
|
|
|
|