Final | 4/21/2008 | 4/21/2008 | 4/21/2008 | P | PASS |
Bob Reichert
|
|
|
loren Phone #: ###-#### correction made, ok to final
|
Final | 4/17/2008 | 4/17/2008 | 4/18/2008 | P | PART |
Bob Reichert
|
|
|
Loren, ###-#### met owner, told shall bond hot and cold water piping per nec 250.104(A) and provide disconnect for water heater per nec 422.31(B), will call back later, rest ok
|
Electrical Rough-In | 9/6/2006 | 9/7/2006 | 9/7/2006 | P | PASS |
Bob Reichert
|
|
|
loren wheeler; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok
|
Electrical Rough-In | 9/5/2006 | 9/6/2006 | 9/6/2006 | A | FAIL |
Jack Frank
|
|
|
loren; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. met owner, 300.4 nail plates and 11/4", 210.52(A)&(E) needs outlet bed rm wall behind door and outside front gfci outlet, 334.15 protect romex expose on post in basement note afci for bed circuits, install smoke detector system, complete all makeup
|
Electrical Rough-In | 10/26/2004 | 10/27/2004 | 10/27/2004 | A | NR |
Jack Frank
|
|
|
Loren-call before you go; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. 312.5(C) see added p/s 10/27/2004 8:28:47 AM
|
Permanent Service | 10/27/2004 | 10/27/2004 | 10/27/2004 | A | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|
Application received | | | 10/7/2004 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/7/2004 | | DONE |
|
|
|
|