Permanent Service | 11/15/2004 | 11/16/2004 | 11/16/2004 | A | PASS |
Bob Reichert
|
|
|
Bill-Service for out building; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner 11/16/2 11/16/2004 9:56:01 AM ok to final. will permit inside later when start wiring. 11/16/2004 9:57:10 AM
|
DOC - Permit Finaled | 11/16/2004 | 11/16/2004 | 11/16/2004 | A | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 11/16/2004 9:57:13 AM
|
Final | 10/21/2004 | 10/21/2004 | 10/21/2004 | P | NR |
William E Thomas
|
|
|
BILL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
not ready should have been canceled 10/21/2004 4:09:44 PM
|
Electrical Rough-In | 10/21/2004 | 10/21/2004 | 10/21/2004 | P | FAIL |
William E Thomas
|
|
|
240.4D-#10awg conductors shall be protected at 30amps
300.5A-no inspection was done to verfy the burial depth
250.52A5-ground rods are required for this installation
200.7C1-grounded conductors shall be reidentified for use as ungrounded conductors
|
Application received | | | 10/19/2004 | | |
|
|
|
|
Issue permit | | | 10/19/2004 | | DONE |
|
|
|
|