Permanent Service | 11/16/2004 | 11/16/2004 | 11/16/2004 | P | FAIL |
Jack Frank
|
|
|
###-#### - jann Note: Garage only cor. posted met owner no violations to be retained original work in violation, no SMS for grds or bonding, 11/2" mast shall not support drop, seal KOs, isolate grds and neuts at sub panel, gfci fro garage recepts, grd recepts to boxes, use manufactures listed breakers only, needs 2 grd rods, #8 cable in 3/4 emt not rated for 50 amps furnace feed shall be #6 11/16/2004 4:03:05 PM
|
Issue PAID IN FULL permit | | | 11/16/2004 | | DONE |
|
|
|
|
Application received | | | 11/16/2004 | | |
|
|
|
|