Third Notice ELE | 1/28/2005 | 1/28/2005 | 1/28/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 1/14/2005 | 1/14/2005 | 1/28/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 11/30/2004 | 1/14/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 11/30/2004 | 11/30/2004 | 11/30/2004 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 11/30/2004 2:43:53 PM
|
Temporary Service | 11/30/2004 | 11/30/2004 | 11/30/2004 | P | PASS |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s o/h new ok 11/30/2004 2:43:49 PM
|
Final | 11/29/2004 | 11/29/2004 | 11/29/2004 | P | FAIL |
Jack Frank
|
|
|
temp power re-inspec.; Phone #: ###-#### Internet Inspection Request from: Heather Packer new cor. posted called left message, 250.64(B) protect #6 GEC , 250.104(C) bond steel trailer someone cut it 11/29/2004 2:39:09 PM
|
Temporary Service | 11/24/2004 | 11/26/2004 | 11/26/2004 | A | FAIL |
Jack Frank
|
|
|
jackie- ###-#### needs grd rod and G E C, remove cord not being used, or terminate in a box 11/26/2004 9:07:45 AM
|
Temporary Service | 11/26/2004 | 11/26/2004 | 11/26/2004 | P | FAIL |
Jack Frank
|
|
|
cor. posted called shall use t/s permit not job permit, 110.12(A) seal all unused KOs, use in use covers, instake bond bushings both ends of emt that GEC is in 250.92(A)(3)
|
Application received | | | 11/23/2004 | | |
|
|
|
|
Issue permit | | | 11/23/2004 | | DONE |
|
|
|
|