Final | 1/10/2005 | 1/10/2005 | 1/10/2005 | P | PASS |
Mike Kinnear
|
|
|
vivian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made ok final 1/10/2005 4:22:23 PM
|
DOC - Permit Finaled | 1/10/2005 | 1/10/2005 | 1/10/2005 | P | PASS |
Mike Kinnear
|
|
|
Finaled by inspector at 1/10/2005 4:22:34 PM
|
Final | 1/6/2005 | 1/7/2005 | 1/7/2005 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/6/2005 at 12:21:36 PM. Contact: ###-####. 440.22 (C) a/c breakers shall not exceed mfgrs value, 314.21 drywall shall be repaired, 406.4 recepts shall be securely fastened 1/7/2005 1:44:25 PM
|
Electrical Rough-In | 12/1/2004 | 12/2/2004 | 12/2/2004 | A | PASS |
Bob Reichert
|
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made, ok to cover. p/s u/g n ok 12/2/2004 8:26:45 AM
|
Rough-In Permanent Service | 11/30/2004 | 12/1/2004 | 12/1/2004 | P | FAIL |
Jack Frank
|
|
|
vivian-- ###-#### or ###-####- gene cor. posted called 300.4, BCC complete all make up, 110.26(F)(2)remove TV and phone from below p/s, 250.148 grd metal boxes, 314.17 use connectors at fange box for cable, 110.3 replace damaged range boxes, 110.12 protect all panels with cover or cardboard 210.25 common area branch circuits? told contractor to worked that out and if they are required 12/1/2004 1:57:42 PM
|
Issue & PRINT permit | | | 11/30/2004 | | DONE |
|
|
|
|
Application received | | | 11/30/2004 | | |
|
|
|
|