Third Notice ELE | 4/11/2005 | 4/11/2005 | 4/14/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 3/31/2005 | 3/31/2005 | 4/11/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 3/17/2005 | 3/31/2005 | | DONE |
|
|
|
|
Final | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | PASS |
Jack Frank
|
|
|
leroy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok 3/17/2005 12:06:35 PM
|
DOC - Permit Finaled | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 3/17/2005 12:06:39 PM
|
Electrical Rough-In | 3/16/2005 | 3/16/2005 | 3/16/2005 | A | PART |
Jack Frank
|
|
|
met contractor showed him all the violations he needs to correct 3/16/2005 9:07:06 AM
|
ELE-Aging Inspection | 3/1/2005 | 3/1/2005 | 3/1/2005 | | FAIL |
Jack Frank
|
|
|
cor. posted called 400.8(1)&(4) shall not use cord for fixed wiring ,or attached to building or structure, 410.30(C)(1) needs cord caps and receptacles, and recepts shall be directly above fixture, also contractor who did work needs to secure permit, the permit for job now is under GL Edwards in Rexburg, he sub contracted the work out to someone else. ###-#### 3/1/2005 9:34:54 AM
|
Application received | | | 11/30/2004 | | |
|
|
|
|
Issue permit | | | 11/30/2004 | | DONE |
|
|
|
|