Telephone call | | | 3/14/2005 | | DONE |
|
|
|
Final cert of value $4,860///3/14/05 BAS
|
Final | 1/5/2005 | 1/5/2005 | 1/5/2005 | P | PASS |
Bob Reichert
|
|
|
Brent; Phone #: ###-#### Internet Inspection Request from: Jan Rice called contr for seismic wires for 3 fixtures. ok to final 1/5/2005 1:55:24 PM
|
DOC - Permit Finaled | 1/5/2005 | 1/5/2005 | 1/5/2005 | P | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 1/5/2005 1:55:27 PM
|
Electrical Rough-In | 12/3/2004 | 12/6/2004 | 12/6/2004 | A | PART |
Pat Lass
|
|
|
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice
walls are ok
Talked to John and he said he would fix the grounding at the panel 12/6/2004 10:10:57 AM
|
Electrical Rough-In | 12/3/2004 | 12/3/2004 | 12/3/2004 | P | FAIL |
Bob Reichert
|
|
|
John-Wall only; Phone #: ###-#### Internet Inspection Request from: Jan Rice 330.30(C) MC cable shall be strapped within 12" of box, 110.3(B) shall use correct strap on conduit, 250.92(B) shall use bonding type locknut thru concentric 12/3/2004 4:23:17 PM
|
Application received | | | 12/3/2004 | | |
|
|
|
|
Issue permit | | | 12/3/2004 | | DONE |
|
|
|
|