Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE04-04033
StatusFinaled
Name L & K ELECTRIC
Site Address 16 N CURTIS RD
Project Name16 N CURTIS - BILLBOARD
Customer Number 
ePlanReview 
Description
Electrical service on billboard sign $750 JRR 12-21-04
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE2/24/20052/24/20052/28/2005 DONE
First Notice has not been responded to.
First Notice Sent 2/7/20052/24/2005 DONE
DOC - Permit Finaled2/7/20052/7/20052/7/2005PPASS
DetailsJack Frank
Finaled by inspector at 2/7/2005 1:06:48 PM
Permanent Service2/7/20052/7/20052/7/2005PPASS
DetailsJack Frank
Re-inspection as per Jack Frank,on service for billboard sign.; Phone #: ###-#### Internet Inspection Request from: Rich Rice
p/s o/h new ok 2/7/2005 1:06:42 PM
Permanent Service1/20/20051/20/20051/20/2005PFAIL
DetailsJack Frank
Re-inspection on sign service after corrections; Phone #: ###-#### Internet Inspection Request from: Rich Rice corrections not made and more created, cor.posted called 250.8 no SMS, 250.90&92 needs meyers hub listed for grounding, 250.64 (B) protect GEC across concrete slab exposed to damage 1/20/2005 2:00:18 PM
Final12/21/200412/22/200412/22/2004AFAIL
DetailsJack Frank
Permanent service for sign; Phone #: ###-#### Internet Inspection Request from: Rich Rice cor. posted called 250.24 terminate GEC to neutral bus, 344 bushing for rigid nipple, 358.42 use approved RT conn. and coup, 250.90&92 use meyers hub listed for bong and grd, 250.52(A)(2) grd steel pole 12/22/2004 9:34:35 AM
Application received  12/21/2004  
Issue permit  12/21/2004 DONE