Second Notice ELE | 2/24/2005 | 2/24/2005 | 2/28/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 2/7/2005 | 2/24/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 2/7/2005 | 2/7/2005 | 2/7/2005 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 2/7/2005 1:06:48 PM
|
Permanent Service | 2/7/2005 | 2/7/2005 | 2/7/2005 | P | PASS |
Jack Frank
|
|
|
Re-inspection as per Jack Frank,on service for billboard sign.; Phone #: ###-#### Internet Inspection Request from: Rich Rice
p/s o/h new ok 2/7/2005 1:06:42 PM
|
Permanent Service | 1/20/2005 | 1/20/2005 | 1/20/2005 | P | FAIL |
Jack Frank
|
|
|
Re-inspection on sign service after corrections; Phone #: ###-#### Internet Inspection Request from: Rich Rice corrections not made and more created, cor.posted called 250.8 no SMS, 250.90&92 needs meyers hub listed for grounding, 250.64 (B) protect GEC across concrete slab exposed to damage 1/20/2005 2:00:18 PM
|
Final | 12/21/2004 | 12/22/2004 | 12/22/2004 | A | FAIL |
Jack Frank
|
|
|
Permanent service for sign; Phone #: ###-#### Internet Inspection Request from: Rich Rice cor. posted called 250.24 terminate GEC to neutral bus, 344 bushing for rigid nipple, 358.42 use approved RT conn. and coup, 250.90&92 use meyers hub listed for bong and grd, 250.52(A)(2) grd steel pole 12/22/2004 9:34:35 AM
|
Application received | | | 12/21/2004 | | |
|
|
|
|
Issue permit | | | 12/21/2004 | | DONE |
|
|
|
|