Temporary Service | 1/6/2005 | 1/7/2005 | 1/7/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/6/2005 at 6:24:12 PM. Contact: ###-####. corrections made t/s u/g n ok 1/7/2005 8:48:45 AM
|
DOC - Permit Finaled | 1/7/2005 | 1/7/2005 | 1/7/2005 | A | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 1/7/2005 8:48:52 AM
|
Temporary Service | 1/4/2005 | 1/5/2005 | 1/5/2005 | A | FAIL |
Bob Reichert
|
|
|
Daniel; Phone #: ###-#### Internet Inspection Request from: Jan Rice called owner and left correction notice. BCC shall post job id sticker. 250.24(A) shall gound grounding electrode conductor to grounded service conductor 1/5/2005 8:27:37 AM
|
(F) Reprint permit | | | 1/5/2005 | | DONE |
|
|
|
|
Application received | | | 12/23/2004 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/23/2004 | | DONE |
|
|
|
|