(F) Reprint permit | | | 1/20/2006 | | DONE |
|
|
|
|
Case Summary (ELE) | | | 1/20/2006 | | DONE |
|
|
|
|
First Notice | | 3/4/2005 | 1/18/2006 | | DONE |
|
|
|
This permit finaled on the web by Tina Payne
|
DOC - Permit Finaled | | | 1/18/2006 | | DONE |
|
|
|
|
Final | 3/3/2005 | 3/4/2005 | 3/4/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/3/2005 at 2:11:42 PM. Contact: ###-####. corrections made. ok to final 3/4/2005 8:22:06 AM
|
Final | 3/1/2005 | 3/2/2005 | 3/2/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/1/2005 at 2:37:58 PM. Contact: ###-####. called contr,358.6 emt fittings shall be listed, 314.15(A) wet locations shall be listed for wet locations, 225.22 raceways shall be raintight in wet locations, left corr notice 3/2/2005 8:52:02 AM
|
Final | 2/22/2005 | 2/23/2005 | 2/23/2005 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/22/2005 at 4:14:38 PM. Contact: ###-####. sign not there, gave t/o, 210.8(B)(2) rooftop rcpt shall be gfci, and bathrooms, 110.26(A)(1) disconnect shall have 3' work clearance 2/23/2005 12:48:59 PM 2/23/2005 12:50:10 PM
|
Electrical Rough-In | 1/21/2005 | 1/21/2005 | 1/21/2005 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/21/2005 at 7:20:03 AM. Contact: ###-####. ok to cover outside sign conduit 1/21/2005 1:47:39 PM
|
Electrical Rough-In | 1/7/2005 | 1/10/2005 | 1/10/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 1/7/2005 at 1:05:47 PM. Contact: ###-####.
walls ok 1/10/2005 11:10:37 AM
|
Issue permit | | | 12/29/2004 | | DONE |
|
|
|
|
Application received | | | 12/29/2004 | | |
|
|
|
|