Final | 3/10/2005 | 3/10/2005 | 3/10/2005 | P | PASS |
Bob Reichert
|
|
|
Jennifer; Phone #: ###-#### Internet Inspection Request from: Jan Rice gfci problem fixed. ok to final 3/10/2005 2:35:09 PM
|
DOC - Permit Finaled | 3/10/2005 | 3/10/2005 | 3/10/2005 | P | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 3/10/2005 2:35:12 PM
|
Final | 3/9/2005 | 3/9/2005 | 3/9/2005 | P | FAIL |
Mike Kinnear
|
|
|
jennifer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore gfci not working 3/9/2005 1:04:44 PM
|
Final | 3/8/2005 | 3/8/2005 | 3/8/2005 | P | FAIL |
Bob Reichert
|
|
|
jennifer -; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 2 bath gfci not working, 1 cfci wired backward. Need to call again 3/8/2005 2:55:48 PM
|
Final | 3/7/2005 | 3/7/2005 | 3/7/2005 | P | FAIL |
Bob Reichert
|
|
|
jennifer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore met with owner, recpts had open grounds in 3 places, gfcis not wired correctly and in wrong place in ckt. Will call again. 3/7/2005 3:51:28 PM
|
Electrical Rough-In | 2/1/2005 | 2/2/2005 | 2/2/2005 | A | CANC |
Bob Reichert
|
|
|
Jennifer; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
Electrical Rough-In | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | PASS |
Bob Reichert
|
|
|
Jennifer; Phone #: ###-#### Internet Inspection Request from: Jan Rice corrections made ric ok 2/2/2005 1:58:03 PM
|
Electrical Rough-In | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | NR |
Bob Reichert
|
|
|
late afternoon please///jennifer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Talked to framer, and owner had to leave, so he wasn't home. He had fixed a portion of the job, but appeared to have quite a bit of work to do before he was ready for an inspection. 2/1/2005 4:16:10 PM
|
Electrical Rough-In | 1/28/2005 | 1/31/2005 | 1/31/2005 | A | FAIL |
Bob Reichert
|
|
|
jennifer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 300.4(D) cable shall 11/4" from edge, 334.23 cable shall be protected within 6' of hatch in attic, 334.24 bend radius 5 times diameter of cable, 334.30 and 314.17C cable shall be supported at intervals of 41/2' and within 8" of each box. Sheath shall be 1/4 " in box. Cable shall not be stapled on edge., 314.29 Junction boxes shall be accessible in attic. 1/31/2005 9:48:10 AM 1/31/2005 9:48:16 AM
|
Electrical Rough-In | 1/21/2005 | 1/24/2005 | 1/24/2005 | A | FAIL |
Bob Reichert
|
|
|
Rich; Phone #: ###-#### Internet Inspection Request from: Jan Rice told owner to recall after floor box is securely mounted and a cable clamp is installed. 1/24/2005 9:20:41 AM
|
Application received | | | 1/19/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 1/19/2005 | | |
|
|
|
|