Third Notice ELE | 3/31/2005 | 3/31/2005 | 4/29/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 3/15/2005 | 3/15/2005 | 3/31/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 2/18/2005 | 3/15/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 2/18/2005 | 2/18/2005 | 2/18/2005 | A | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 2/18/2005 10:13:02 AM
|
Final | 2/17/2005 | 2/18/2005 | 2/18/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day corrections made, ok to final 2/18/2005 10:13:00 AM
|
Electrical Rough-In | 2/10/2005 | 2/11/2005 | 2/11/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 4:56:31 PM. Contact: ###-####. 110.26(A)(1) depth of work space shall be 3', 358.26 there shall be max 360 degree bends, 348.30 fmc shall be supported witin 12" of box, 210.63 gfci shall be provided on roof for refrigeration units, 110.3(B) equipment shall be listed 2/11/2005 11:51:54 AM
|
Application received | | | 2/4/2005 | | |
|
|
|
|
Issue permit | | | 2/4/2005 | | DONE |
|
|
|
|