Second Notice ELE | 3/15/2005 | 3/15/2005 | 3/22/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 2/24/2005 | 3/15/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 2/24/2005 | 2/24/2005 | 2/24/2005 | A | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 2/24/2005 8:56:54 AM
|
Final | 2/23/2005 | 2/24/2005 | 2/24/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/23/2005 at 4:22:00 PM. corrections made, clg now ready, so this job is ok to final 2/24/2005 8:56:26 AM
|
Final | 2/22/2005 | 2/23/2005 | 2/23/2005 | A | NR |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/22/2005 at 2:16:45 PM. Contact: ###-####. 330.30(B) mc cable shall be supported within 12" of boxes, 358.26 emt shall not have over 360 degree bends, 440.14 disconnects shall be lockable if on panel, 408.4 circuit directory shall be provided. when call again, all recpts to be made-up if want final. 2/23/2005 10:38:11 AM
|
Electrical Rough-In | 2/7/2005 | 2/7/2005 | 2/7/2005 | P | PASS |
Bob Reichert
|
|
|
Rick; Phone #: ###-####=-call ahead of time so he can let you in Internet Inspection Request from: Jan Rice ok to cover walls only. told elect to use gnd screws in boxes, not sheet metal. 2/7/2005 2:41:37 PM
|
Issue permit | | | 2/7/2005 | | DONE |
|
|
|
|
Application received | | | 2/4/2005 | | |
|
|
|
|