Permanent Service | 2/25/2005 | 2/25/2005 | 2/25/2005 | P | PASS |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice p/s o/h exst ok, corrections were made 2/25/2005 3:59:17 PM
|
Permanent Service | 2/9/2005 | 2/9/2005 | 2/9/2005 | P | NR |
Jack Frank
|
|
|
Lars; Phone #: ###-#### Internet Inspection Request from: Jan Rice needs GEC termianted at 1st 5 ft of u/g water pipe front NW bed rm downstairs see added r/i 2/9/2005 12:28:33 PM
|
Electrical Rough-In | 2/9/2005 | 2/9/2005 | 2/9/2005 | P | PASS |
Jack Frank
|
|
|
r/i for garage ok
|
Electrical Rough-In | 2/7/2005 | 2/7/2005 | 2/7/2005 | P | FAIL |
Bob Reichert
|
|
|
mike ###-#### 230.82 There shall be only service conductors on main lugs. They have no overcurrent protection. 2/7/2005 1:55:49 PM
|
Issue permit | | | 2/7/2005 | | DONE |
|
|
|
|
Application received | | | 2/7/2005 | | |
|
|
|
|