Final | 5/5/2005 | 5/5/2005 | 5/5/2005 | P | FAIL |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted met owner 410.8 clearence closet fixture, 406.4 recepts not secure and flush with plate, 110.3(B) use manufacures breakers only 5/5/2005 3:22:32 PM
|
Electrical Rough-In | 3/3/2005 | 3/4/2005 | 3/4/2005 | A | FAIL |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Barbara Moore all of the corrections not made 3/4/2005 8:33:37 AM
|
Electrical Rough-In | 3/4/2005 | 3/4/2005 | 3/4/2005 | P | PASS |
Jack Frank
|
|
|
Mark; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok 3/4/2005 1:41:15 PM
|
Electrical Rough-In | 3/1/2005 | 3/2/2005 | 3/2/2005 | P | FAIL |
Jack Frank
|
|
|
Mark; Phone #: ###-#### Internet Inspection Request from: Jan Rice cor. posted met owner 300.14 free length, 300.4 (A)(1)&(D), 310.15 derate wires in nipple over 24", 110.14 needs device for splices and use listed devices listed when mixing copper and alum 3/2/2005 4:58:09 PM
|
Conference | 2/22/2005 | 2/23/2005 | 2/23/2005 | P | DONE |
Jack Frank
|
|
|
###-#### - MARK owner needs bld permit 2/23/2005 3:53:09 PM
|
Issue & PRINT permit | | | 2/22/2005 | | DONE |
|
|
|
|
Application received | | | 2/22/2005 | | |
|
|
|
|