Final | 5/19/2005 | 5/19/2005 | 5/19/2005 | P | PASS |
Bob Reichert
|
|
|
CHRIS; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
Final | 5/11/2005 | 5/11/2005 | 5/11/2005 | P | FAIL |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 110.2 humidifier shall be approved, listed llabelled, identified
|
Final | 3/15/2005 | 3/16/2005 | 3/16/2005 | A | CANC |
Bob Reichert
|
|
|
cHRIS; Phone #: ###-#### Internet Inspection Request from: Jan Rice see added insp. this for r/i 3/16/2005 10:16:10 AM
|
Rough-In Permanent Service | 3/16/2005 | 3/16/2005 | 3/16/2005 | A | PASS |
Bob Reichert
|
|
|
corrections made, left survey for staple romex. ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/1/2005 | 3/1/2005 | 3/1/2005 | P | FAIL |
Bob Reichert
|
|
|
chris ###-#### 314.17(C) nm cable shall be 1/4" inside box, 314.17(A) shall provide cable connector at boxes where 1/2" ko is used, 300.4(D) nm cable shall be 1 1/4" from the edge of framing members, 110.12(C) there shall be no broken boxes(broken out clamps), 314.20 boxes shall be flush with surface, framing shall not be torn out and wire left hanging. BCC job id sticker shall be posted., called contr, left corr notice 3/1/2005 12:54:55 PM
|
Application received | | | 3/1/2005 | | |
|
|
|
|
Issue & PRINT permit | | | 3/1/2005 | | |
|
|
|
|