Final | 7/14/2005 | 7/14/2005 | 7/14/2005 | P | PASS |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ok to final
|
Final | 7/1/2005 | 7/1/2005 | 7/1/2005 | P | FAIL |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 352.30(A) rnc shall be strapped within 3' of box,404.9,406.5,314.21 faceplates shall completely cover openings and seat against finished surfaces, (microwave, gec cover, recpts in bedroom), 210.70(A)(2)(a) light shall be in stairway, called contr, left corr notice,
|
Permanent Service | 3/23/2005 | 3/23/2005 | 3/23/2005 | A | PASS |
Mike Kinnear
|
|
|
p/s u/g n ok
|
Electrical Rough-In | 3/22/2005 | 3/23/2005 | 3/23/2005 | A | PASS |
Mike Kinnear
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Electrical Rough-In | 3/21/2005 | 3/21/2005 | 3/21/2005 | P | FAIL |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 300.4(D) nm cable shall be 1 1/4" from edge of framing member, North of fireplace, down low. 314.23(B)(1) boxes shall be securely fastened, North wall of garage, and North of garage door 3/21/2005 12:41:26 PM
|
Rough-In Permanent Service | 3/1/2005 | 3/1/2005 | 3/1/2005 | P | FAIL |
Bob Reichert
|
|
|
chris ###-#### 300.4(D) nm cable shall be 1 1/4" from sdge of framing member, 314.23(B)(1) boxes shall be fastened, 314.23(B)(2) metal braces shall be fastened, BCC job id sticker shall be posted 3/1/2005 1:29:49 PM
|
Application received | | | 3/1/2005 | | |
|
|
|
|
Issue & PRINT permit | | | 3/1/2005 | | DONE |
|
|
|
|