Final | 4/28/2005 | 4/29/2005 | 4/29/2005 | A | PASS |
Jack Frank
|
|
|
bill -- re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 4/29/2005 8:23:56 AM
|
DOC - Permit Finaled | 4/29/2005 | 4/29/2005 | 4/29/2005 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 4/29/2005 8:24:01 AM
|
Final | 4/27/2005 | 4/28/2005 | 4/28/2005 | A | FAIL |
Jack Frank
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called use manufactures listed breakers only 110.3(B), 210.52(A) shall address outlet spacing old part of house where new doors were added told him about that 03-02-05 on correction posted then 4/28/2005 9:22:08 AM
|
Electrical Rough-In | 3/17/2005 | 3/17/2005 | 3/17/2005 | P | PASS |
Jack Frank
|
|
|
Bill-underground; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok 3/17/2005 2:29:36 PM
|
Conference | 3/15/2005 | 3/16/2005 | 3/16/2005 | A | DONE |
Jack Frank
|
|
|
gordon; Phone #: ###-#### Internet Inspection Request from: Barbara Moore contractor called I answered his questions over the phone 3/16/2005 10:26:47 AM
|
Electrical Rough-In | 3/3/2005 | 3/4/2005 | 3/4/2005 | A | PASS |
Jack Frank
|
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore r/i ok still needs to address u/g installed by excavation contractor 3/4/2005 10:03:48 AM
|
Rough-In Permanent Service | 3/2/2005 | 3/2/2005 | 3/2/2005 | P | FAIL |
Jack Frank
|
|
|
bill-- ###-#### cor. posted called 300.4, 250.122 use # 12 for grd pigtail 3 gang switch back door, 250.52(A)(1) 104(A)(1) grd or bond p/s old house water system 210.52(A) address outlet spacing old part of house where spacing changed because of new opening, uncover all u/g install by excavation contractor, have electrical contractor install it and call for inspection, also have approved plans at job site 3/2/2005 2:00:06 PM
|
Issue & PRINT permit | | | 3/2/2005 | | DONE |
|
|
|
|
Application received | | | 3/2/2005 | | |
|
|
|
|