Final | 5/26/2005 | 5/26/2005 | 5/26/2005 | P | PASS |
Bob Reichert
|
|
|
alex; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
Rough-In Permanent Service | 4/12/2005 | 4/13/2005 | 4/13/2005 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/12/2005 at 10:40:10 PM. Contact: ###-####. already had ri, see added insp for p/s 4/13/2005 9:45:24 AM
|
Permanent Service | 4/13/2005 | 4/13/2005 | 4/13/2005 | A | PASS |
Bob Reichert
|
|
|
corrections made, p/s o/h n ok
|
Rough-In Permanent Service | 4/11/2005 | 4/12/2005 | 4/12/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/11/2005 at 7:45:14 PM. Contact: ###-####. talked to owner, left corr. notice, 250.24(A)(5) a grounding connection shall not be made to any grounded conductor on the load side of the service disconnect 4/12/2005 10:29:25 AM
|
Rough-In Permanent Service | 4/10/2005 | 4/11/2005 | 4/11/2005 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/10/2005 at 10:04:34 PM. Contact: ###-####. met with owner, outside ready, but he needs to provide ground lug inside at sub-panel 4/11/2005 3:48:29 PM
|
Rough-In Permanent Service | 4/10/2005 | 4/11/2005 | 4/10/2005 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/10/2005 at 9:58:48 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Apr 10 2005 10:01PM.
|
Electrical Rough-In | 3/10/2005 | 3/11/2005 | 3/11/2005 | P | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 3/10/2005 at 10:10:50 PM. Contact: ###-####.
ri ok
p/s not yet ready, spoke with the owner about the grounding and guide wire supports for service. 3/11/2005 12:27:24 PM
|
Electrical Rough-In | 3/7/2005 | 3/8/2005 | 3/8/2005 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/7/2005 at 11:39:56 AM. Contact: ###-####. part cor. posted met owner remove range hood amd vaccum outlet from kit circuit remove panel from warm wall address out spacing , 2 walls , countertop spacing, 300.4 nail plates and 11/4 inches staple romex with 8 or 12 inches of boxes, remove ironing board from MB circuit, grd metal boxes finish all wiring remove low volt from high volt door bell xformer 3/8/2005 11:40:35 AM
|
Rough-In Permanent Service | 3/4/2005 | 3/7/2005 | 3/7/2005 | A | CANC |
Bob Reichert
|
|
|
cameron ###-#### told cameron to have homeowner meet me on job for a conference 3/7/2005 9:59:30 AM
|
Application received | | | 3/4/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 3/4/2005 | | DONE |
|
|
|
|