Second Notice ELE | 5/26/2005 | 5/26/2005 | 5/27/2005 | | DONE |
|
|
|
This permit finaled on the web by Dan Mitchell
|
First Notice Sent | | 5/13/2005 | 5/26/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 5/13/2005 | 5/13/2005 | 5/13/2005 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 5/13/2005 8:10:58 AM
|
Final | 5/12/2005 | 5/13/2005 | 5/13/2005 | A | PASS |
Jack Frank
|
|
|
Corrections have been performed. Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 5/13/2005 8:10:53 AM
|
Conference | 3/30/2005 | 4/4/2005 | 4/4/2005 | A | DONE |
Jack Frank
|
|
|
Owner requests a conference with you and me today at 8:30 AM on the job site to see exactly how far we have to go with updates.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 4/4/2005 10:19:34 AM
|
Final | 3/9/2005 | 3/10/2005 | 3/10/2005 | A | FAIL |
Jack Frank
|
|
|
We replaced the existing burnt-up pole-mounted fused disconnect and RV receptacle with a new circuit breaker/RV receptacle combo for Space # 10.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. posted called 550.32,10 needs 100 amp p/s and cord shall meet requirements of 550.10 needs 2 grd rod for p/s 110.26 needs clearence for p/s phone box below it, 230.24 o/h needs required clearences no violations retained also install GEC taps as 250.64(D) states 3/10/2005 9:51:24 AM
|
Application received | | | 3/9/2005 | | |
|
|
|
|
Issue permit | | | 3/9/2005 | | DONE |
|
|
|
|